Short Circuit Indicator type VE

[Home] [Back] [General Description] [Contact]
Design
The short circuit indicator type VE or VEE consists of a "detecting set" and a reading instrument. The reading instrument is available either as a surface mounted instrument ( VE type) or as a panel instrument ( VEE type). For both versions a remote indication contact is possible.
The detecting set consists of three single sensors. The output of these sensors is combined in one junction and connected to the reading instrument.

Function
The sensors are mounted on a potential- free high voltage cable. In case of a fault, the short circuit current induces an impulse into the metering coil, which is installed inside the housing of the sensor. This impulse is transmitted to the reading instrument, if the impulse level has reached or overshot the preadjusted operating point. The operating point is adjustable in each sensor. The reading instrument is equipped with a bistable flag indicator for each core. The impulse which is transmitted from the sensor energizes the flag indicator and a red painted plate becomes visible (short circuit indication). The indication is reset through a magnetic-mechanic equipment. An auxiliary magnet is being placed near the indication flag. Therefore the flag indicator reverses its polarity and a black plate becomes visible.The indicator is then reset. This version needs no auxiliary power supply.

Short Circuit Indicator type VE -fig1

Assembling
The sensors are installed with steel frames on the cable. For this purpose, the frame must be disconnected from the sensor housing. Then the frame must be laid around the cable and has to be connected to the housing again with two screws. After aligning the sensor, the sensor must be fixed on the cable.
The metering cable, coming from the sensor has to be wired according to the terminal table shown on the reading instrument.

a) Surface-Mounted Instrument
The surface mounted housing has to be fixed with two screws according
to figure 1. The cable input for the connection cable is either on the down side or on the backside of the reading instrument.

Connections
terminal 1 = sensor wire = white remote indication
terminal 2 = sensor wire = brown terminal 11
terminal 3 = sensor wire = green terminal 12
terminal 4 = sensor wire = yellow terminal 13
b) Panel-Mounted Instrument
The panel instrument (type VEE) has to fit into a panel cutout with the dimension of 68+0.7 x 68+0.7 mm ( DIN ). Spring clamps are used to fix the housing in the cutout (figure 2).
Short Circuit Indicator type VE -fig2
Connections
terminal 1 = sensor wire = white remote indication
terminal 2 = sensor wire = brown terminal 7
terminal 3 = sensor wire = green terminal 8
terminal 4 = sensor wire = yellow terminal 9
Technical Data
operating current: n.a.
operating point: 300...1500 A +/- 10%
temperature range: -20° to + 70°C
relay contact: max. 220V AC switching power 50...150W
Dimension ( W*H*D) surface mounted: 76 x 140 x 42 mm
  panel instrument: 96 x 48 x 63 mm
sensor: 38 x 38 x 26 mm










EMG Elektro-Mechanik GmbH - Ringstr. 4 - D-42553 Velbert / Germany