Design
The short circuit indicator type MF consists of:
1 pc. reading instrument
3 pcs. sensors
connection cable
The reading instrument is available as a panel- mounted instrument and
as a surface- mounted instrument. Both versions can be equipped with a
remote indication contact.
The set of sensors (version MFS) consists of three single sensors. The
cable output of these sensors is combined in one junction. The cable
length from this junction point to the reading instrument is 3000 mm
(standard - on request other lengths are possible, too).
The light mains sensors (version MFL) are connected to the reading
instrument with light mains ( standard length 1400 mm - other lengths
are possible, too).
|
Function
The sensors are installed on the medium voltage cables.
In case of a short circuit, a coil, which is mounted into the sensor's
housing, is being energized. This coil transmits an impulse to the
reading instrument. Within the reading instrument the impulse is
evaluated.
Minimum impulse adjustment: The reading instrument is equipped with a
setting for minimum impulse duration. The impulse picked up from the
sensor is checked for its length. If the impulse length is shorter than
the adjusted mininum impulse duration, no fault will be indicated. If
the impulse length is longer than the preadjusted duration, a short
circuit is indicated.
This equipment allows filtering peak currents caused by switch currents
or similar circumstances. Wrong indications are avoided.
The reset of the earth fault or short circuit indication can be done in
the following ways:
a) automatic time reset: A time element controls the indication and
resets it after a preadjusted time (3 values between 0.5 h to 40 h are
selectable).
b) manual reset with a push-button
c) recovering net voltage (if the reading instrument is supplied from
the monitored net.
|
Assembling
(please refer to the assembling instruction)
The sensors are installed on the conductors with steel frames. For this
purpose, the frame has to be disconnected from the sensor housing and
has to be placed around the high voltage core. After this, the sensor
has to be fixed in its final position.
a.) surface- mounted instrument
The surface- mounted instrument has to be fixed with two screws. The
connection cable can be inserted into the terminal box of the reading
instrument from the back side or from the bottom of the housing.
b.) panel- mounted instrument
The panel mounted version has to be pushed into a prepared cutout of a
panel. (dimensions of the cutout: 91.5+0.8
* 44.5 +0.6
mm). The housing of the reading instrument is equipped with spring
clamps (standard; please refer to figure 1). It has to be pushed into
the cutout with a little pressure.
|
 |
Technical
Data
operating current: short circuit: 150A to 1500A
Dimensions
( W * H * D )
accuracy: +/- 10 %
reading instrument:
temperature range: -20°C to +70°C
panel-mounted instrument 96*
48*63 mm
reading instrument: reset time delay: 0.5h to 40h
surface-mounted
instrument 76*140*42 mm
power request: stand by mode: 5-10µA
sensor:
indication mode: 60µA
short circuit
sensor 38* 38*26 mm
power supply: selectable:
- 230 V AC
Protection
class
(also possible with accumulator)
panel-mounted instrument IP 46
- 9 V to 110 V DC
surface-mounted instrument IP 65
- lithium battery
sensors IP 67
remote indication: max. 230 V AC / 50 W to 150 W
|
|

|
|

|
EMG Elektro-Mechanik GmbH - Ringstr. 4 - D-42553 Velbert / Germany
Tel: +49-2053-422890 - Fax: +49-2053-422899 - Email: kus@emg-ger.com
|
|

|
|
|