Assembling
The place of assembly must be “switched off”
according to instructions!
Please choose the requested reset time before the assembly. The short
circuit direction indicator must be installed on unscreened cables only. The indicator must be fixed directly on the
cable. For this purpose, the screws (2) are loosened so much that the
frame tape (1) can be withdrawn from the terminal board (3) .
The frame tape must be wrapped around the cable,
fixed under the terminal board (3) and then pulled so much, that the rubber rings (5) are exposed to pressure.
The terminal board (3) has to be
screwed with the screws (2). The projecting steel tape is bend sharply backwards
and then bend backwards around the cable.
Please make sure that the short circuit direction indicator will be
mounted according to the suitable cable dimension (refer to label on
the KRA).
Technical Data
Dimensions of the housing: (W*H*D*) = 44*53*28 mm
Operating current: 150A to 1000A (adjustable)
Precision: +/- 10%
Reset time: 3 times between 0,5h and 20h
(must
be indicated with the order)
Temperature range: -20 to +70°C
Power supply: no auxiliary power supply
Power request: 20μA
|