Short Circuit Indicator Type K / KH / KM

[Home] [Back] [General Description] [Contact]
Design
The electronic wiring and the flag indication is incorporated in the housing of the short circuit indicator. The stainless steel frame fixes the reading instrument on the core. It is possible to disconnect the frame from the housing. When the reading instrument is in its final position on the core, one or two fixing screws on the frame save this postion.
For bigger diameters of the core, the frame must be turned up.
Therefore, two bending positions are marked on the frame.
The indicator has a high resistance to atmospheric conditions, for this reason the flag indication and the electronic wiring are absolutly sealed
.


Function
The short circuit indicator has to be mounted on high-voltage cables.
In case of a short circuit, a coil in the sensor will detect the peak current impulse.
If the pre-adjusted operating point is reached, the evaluation-electronics will stimulate the flag indicator.
A "red surface" is the signal for a detected short circuit.

With the indicator type K, the nescessary power for auto reset
will be gained from the electrical field, which is around the high voltage core. This unidirectional power charges a capacitor.
The capacitor becomes discharged over an arrestor and
the reset coil of the indicator. After the reset, the indicator
shows a black face. The approximate charging time, i.e. the reset time, is shown in the diagramme on the right hand. The charging time of the capacitor depends on the local situation.

The short circuit indicator type K can be provided with a multiple adjustment for trip currents.
With the indicator type KH, the indication flag will be reset with
the help of a magnetic system. Via a test button, a magnet is being moved, which will then cause the indication flag to reset.
The short circuit indicator type KM resets automatically and manually.

 

Short Circuit Indicator Type K / KH / KM -diagramme
Assembling
The short circuit indicator is fixed on the high voltage cable with the stainless steel frame. For mounting, the frame must be disconnected from the housing. After the frame has been laid around the cable, it must be screwed on the sensor housing again. There are one or two screws on the frame for fixing the sensor in its final position.

Technical Data
dimensions of the sensor housing:
short circuit indicator type K / KH / KM ( W*H*D ) 40 * 50 * 38 mm
operating current:   150 ....1500 A
precision:   + / - 10 %
temperature range:   - 40 to + 70° C
material of fixing frame:   stainless steel

EMG Elektro-Mechanik GmbH - Ringstr. 4 - D-42553 Velbert / Germany
Tel: +49-2053-422890 - Fax: +49-2053-422899 - Email: kus@emg-ger.com