Application
This earth fault and short circuit indicator is a combined instrument for detecting earth fault and short circuits.
This indicator operates in medium voltage radial networks with one input. The earth fault current in resistance- earthed or fixed earthed networks must be 20 A as a minimum (10 A with special version).
This indication system should be installed at all branch points and passing lines of the network.
The special feature of this instrument is that the connections between the sensors and the reading instrument are done via light mains. This is an advantage because the sensors can be mounted directly in the unscreened area of the cable. Accordingly, the screen does not have to be led back through the frame, respectively through the steel tape.
|
 |
|
General Description
The indicator is available as a panel-mounted instrument.
The indicator set consists of one reading instrument,
four sensors and four fibre optic cables.
The earth fault- and short circuit indicator summarizes two ways of fault search:
1.) detection of short circuits
2.) detection of earth faults fault.
|
|
|
|
version
|
number of operating points
|
| earth fault |
short circuit |
| E |
1 |
1 |
| F |
7 |
7 |
|
|
The fault can be indicated as follows:
a) type EKL8000-1: earth fault and short circuit via one LED each
b) type EKL8000-3: short circuit via one LED for each core, one LED for earth fault for a) and b): remote indication for earth fault and short circuit via one relay contact. |
|
|
The Versions "E" and "F" of the earth fault- and short circuit indicator type EKL 8000 are constructed identically.
The difference is the number of operating points for earth fault and / or short circuit indication which can be chosen
(confer table).
Every instrument is equipped with a contact for remote indication as a permanent contact (1 x changer).
(Wipper contact is availabe by special request.)
|
|
|
Earth Fault and Short Circuit Indicator
type EKL 8000
|
|
core
diameter
(mm)
|
EKL 8000-1
|
EKL 8000-3
|
|
version
|
version
|
|
E
|
F
|
E
|
F
|
|
5 - 15
|
22.13.11
|
22.14.11
|
22.16.11
|
22.17.11
|
|
15 - 25
|
22.13.12
|
22.14.12
|
22.16.12
|
22.17.12
|
|
25 - 35
|
22.13.13
|
22.14.13
|
22.16.13
|
22.17.13
|
|
35 - 45
|
22.13.14
|
22.14.14
|
22.16.14
|
22.17.14
|
|
45 - 55
|
22.13.15
|
22.14.15
|
22.16.15
|
22.17.15
|
|
55 - 65
|
22.13.16
|
22.14.16
|
22.16.16
|
22.17.16
|
|
Steel
belt*
|
22.13.18
|
22.14.18
|
22.16.18
|
22.17.18
|
* advise cable diameter by ordering
|
|
|
|
|
Order Data
Earth Fault and Short Circuit Indicator type EKL 8000
|
|
| operating points short circuit: |
| 200 / 300 / 400 / 500 / 600 / 800 / 1000 A ** |
| reset delay: |
(h)______
|
| minimum impulse duration: |
(ms)______
|
| power supply |
:(V)______ |
| length of fiber optic cables |
:(mm)_____
|
|
order number
|
:________
|
|
earth fault sensor
|
| operating points earth fault: |
| 10 / 20 / 30 / 40 / 50 / 60 / 80 / 100 A** |
| cable diameter |
:(mm)_______
|
| cable length |
:(mm)_______
|
|
order number
|
:________
|
**standard - other values can be chosen by special request |
|
|
|
|
|
|
|
|
|