|
|
|
Application
The earth fault and short circuit indicator type EKL3.2 is a combined instrument for detecting earth faults and short circuits.
This indicator is used in medium voltage radial networks with one input. The earth fault current in resistance-earthed or solidly earthed neutral systems must be 10 A as a minimum. This indication system should be installed in each branch of the network.
The fault can be indicated as follows:
a) short circuit - with one LED for each core
b) earth fault - with one LED
c) one remote indication for earth fault and short
circuit via a potential-free relay contact.
|
|
 |
|
General Description
The indicator is available as a panel mounted (1) or surface mounted (2) device. The indicator set consists of one reading instrument (1,2), four sensors (4), fiber optic cables (3) and a copper cable (5).
The earth fault- and short circuit indicator summarizes two ways of fault search:
1.) detection of short circuits
2.) detection of earth faults
|
|
|
|
|
version
|
number of operating points
|
| earth fault |
short circuit |
| E |
1 |
1 |
| F |
6 |
7 |
|
|
The Versions "E" and "F" of the earth fault- and short circuit indicator type EKL3.2 are constructed identically. The difference is the number of operating points for earth fault and / or short circuit indication which can be chosen (confer table).
Every instrument is equipped with a contact for remote indication as a permanent contact (1 x changer).
(Wipper contact is availabe by special request.) |
|
|
|
Earth Fault and Short Circuit Indicator type EKL3.2
|
|
core
diameter
(mm)
|
surface mounted
|
panel mounted
|
earth fault sensor
|
|
version
|
version
|
one-
core
cable
|
three-
core
cable
|
|
E
|
F
|
E
|
F
|
|
5 - 15
|
22.07.11
|
22.21.11
|
22.08.11
|
22.23.11
|
12.07.11
|
12.06.11
|
|
15 - 25
|
22.07.12
|
22.21.12
|
22.08.12
|
22.23.12
|
12.07.12
|
12.06.12
|
|
25 - 35
|
22.07.13
|
22.21.13
|
22.08.13
|
22.23.13
|
12.07.13
|
12.06.13
|
|
35 - 45
|
22.07.14
|
22.21.14
|
22.08.14
|
22.23.14
|
12.07.14
|
12.06.14
|
|
45 - 55
|
22.07.15
|
22.21.15
|
22.08.15
|
22.23.15
|
12.07.15
|
12.06.15
|
|
55 - 65
|
22.07.16
|
22.21.16
|
22.08.16
|
22.23.16
|
12.07.16
|
12.06.16
|
|
Steel
belt*
|
22.07.18
|
22.21.18
|
22.08.18
|
22.23.18
|
12.07.18
|
12.06.18
|
* advise cable diameter by ordering
|
|
|
Order Data
Earth Fault and Short Circuit Indicator type EKL3.2
|
|
| operating points short circuit: |
| 200 / 300 / 400 / 500 / 600 / 800 / 1000 A ** |
| reset delay: |
(h)______
|
| minimum impulse duration: |
(ms)______
|
| power supply |
:(V)______ |
| length of fiber optic cables |
:(mm)_____
|
|
order number
|
:________
|
|
earth fault sensor
|
| operating points earth fault: |
| 10 / 20 / 30 / 40 / 50 / 60 A** |
| cable diameter |
:(mm)_______
|
| cable length |
:(mm)_______
|
|
order number
|
:________
|
**standard - other values can be chosen by special request |
|
|
|
|
|
|
|
|
|
|