Design
The earth fault and short circuit indicator consists of:
3 pcs. short circuit sensors
1 pc. earth fault sensor
1 pc. reading instrument
connecting cables and / or light mains
The reading instrument is
incorporated in a plastic housing together with the electronics for the
time reset and the evaluating electronics.
Earth faults are indicated with a blinking LED. Short circuits are
indicated with one blinking LED per cable.
The fault is remote indicated via one relay (1x changer) for earth
fault- and short circuit indication.
The reading instrument is equipped with a test/reset button.
Each sensor consists of a plastic housing, which contains a coil to
detect impulses caused by a short circuit or earth fault.
Depending on the version, a connection cable is fixed to the sensor, or
the sensor is prepared for connection to a light mains. The housing is
fully sealed and follows the standards of IP 67.
The light mains are applied for a potential-free data transmission
between the short cicuit sensor and the reading instrument through a
high voltage area. These light cables are made of PMMA and are
available up to a length of 15 m.
Function
The
sensors detect earth faults and short circuits inductively. The
operating points for earth fault and short circuit are adjusted with a
threshold level electronic. When the current exceeds the preadjusted
threshold level, an impulse is sent to the reading instrument for
evaluation. The respective LED is activated and starts to blink.
Minimum impulse adjustment: The reading instrument is equipped with a
setting for minimum impulse duration. The impulse picked up up from the
sensor is evaluated for its duration. If the impulse length is shorter
than the adjusted value for the mininum impulse duration, no fault will
be indicated. If the impulse duration is longer than the preadjusted
duration, an earth fault or short circuit will be indicated.
This equipment allows the filtering of peak currents caused by switch
currents or similar circumstances. Wrong indications are thus avoided.
With the instrument 4 values for minimum impulse duration can be
adjusted (times follow request of customer).
The reset of the earth fault or short circuit indication can be done
over:
a) automatic time reset: A time element controls the indication and
resets it after a preadjusted time (4 values between 0.5 h and 40 h are
selectable).
b) manual reset with a push-button
c) recovering net voltage (if the reading instrument is supplied from
the monitored net).
Assembling
-
Please refer to assembling instructions delivered with each instrument -
The reading instrument has to be installed outside the high voltage
area. It is possible to install the short circuit sensors on screened
and unscreened cables. The earth fault sensor must be installed around
all three cores to assure that the sum current of all the three cables
is picked up.
The frames of the sensors can be opened for installation.
The short circuit sensors are connected to the reading instrument via
light mains.
The earth fault sensor is connected to the reading instrument via cable.
|