Design
The capacitive voltage ledge consists of a plasic housing which
incorporates a measuring circuit component. The capacitive voltage
ledge is a part of the voltage detection system (VDS) .
The VDS-system is designed according to IEC 61243-5.
Function
The voltage coming out of the bushing / capacitive insulator is limited
in the capacitive voltage ledge according to the regulations of IEC
61243-5. The balancing measuring circuit component must always be
adapted to the assigned bushing / capacitive insulator. For this
purpose, the current coming out of the bushing / capacitive insulator
has to be measured (confer Appendix D).
Assembling
The housing is fixed with two screws on the front side of the housing.
The connections for the coupling electrodes (voltage pick-up in the
bushing or in the capacitive insulator) and the earth connection are on
the backside of the capacitive voltage ledge. The cables are connected
through flat-plugs 6.3 x 0.8 mm. The terminals are protected from water
through protection tulles. The measuring circuit component is installed
inside the housing.
The panel cut-out for the KS-housing must be accomplished according to
figure BN002.
Technical
Data
port conditions: HR-System
rated frequency: 50 Hz
port voltage: 70 – 90 V
port current: 2.5 µA
protection class: IP 65
temperature range: -25° to 65°C